Skip to main content
← Vulnerabilities

A vulnerability has been identified in SIMATIC BATCH V9.1 (All versions), SIMATIC Information Server 2020 (All versions), SIMATIC…

7.5HighCNA
Exploited
No known exploitation
Fix
No fix listed
Who is exposed
Specific setups only

Do first: Check whether your setup matches what the bug needs. Affected products include SIMATIC BATCH V9.1, Information Server 2020/2022, PCS 7 V9.1, Process Historian 2020/2022, WinCC V7.5/V8.0/V8.1 and WinCC Runtime Professional V17-V21 (all versions). Remote user authentication uses the deprecated NTLM protocol and is not properly secured. Kerberos is not used (for example, no domain with a Server Principal Name set).

Published
Last modified
Reference
Last checked
26/100 · provisional
Specific setups only
None on Exploit-DB, Metasploit or GitHub
  • Exploitation: none
  • Automatable: no
  • Technical impact: total

Summary

This vulnerability affects several Siemens SIMATIC products, including WinCC, PCS 7, BATCH, Information Server, and Process Historian. A remote attacker who can position themselves between a user and the system, without logging in and with the user's involvement, can relay NTLM authentication to impersonate a legitimate user, and the resulting impact depends on which services are reachable, such as a SQL server used by WinCC.

Written by anthropic/claude-haiku-5.5 from the sources below. Verify against them.

Read the original description

A vulnerability has been identified in SIMATIC BATCH V9.1 (All versions), SIMATIC Information Server 2020 (All versions), SIMATIC Information Server 2022 (All versions), SIMATIC PCS 7 V9.1 (All versions), SIMATIC Process Historian 2020 (All versions), SIMATIC Process Historian 2022 (All versions), SIMATIC WinCC Runtime Professional V17 (All versions), SIMATIC WinCC Runtime Professional V18 (All versions), SIMATIC WinCC Runtime Professional V19 (All versions), SIMATIC WinCC Runtime Professional V20 (All versions), SIMATIC WinCC Runtime Professional V21 (All versions), SIMATIC WinCC V7.5 (All versions), SIMATIC WinCC V8.0 (All versions), SIMATIC WinCC V8.1 (All versions). Affected systems do not properly secure their remote user authentication with the deprecated NTLM protocol. This could allow unauthenticated remote attackers, who have achieved a machine in the middle position, to relay NTLM authentication and impersonate a legitimate user. The potential impact depends on the services that are accessible, e.g. a SQL server used by WinCC.

cve.now Index

26Pcve.now Index 26 of 100 · methodology v3 · provisional
  • Exploitation0/40No signal
  • Exposure12/25Specific setups only, reachable over the network without a login
  • Reach?/20Unknown. No tracked technology or package matched
  • Severity8.5/10CVSS 7.5, total technical impact per CISA
  • No patch5/5No patch listed yet

What would change the score

  • Would score about 76 if added to CISA KEV
  • Would score about 71 if CISA's SSVC rates exploitation active

What to do

  • Check whether your setup matches what the bug needs.

    Affected products include SIMATIC BATCH V9.1, Information Server 2020/2022, PCS 7 V9.1, Process Historian 2020/2022, WinCC V7.5/V8.0/V8.1 and WinCC Runtime Professional V17-V21 (all versions). Remote user authentication uses the deprecated NTLM protocol and is not properly secured. Kerberos is not used (for example, no domain with a Server Principal Name set).
  • Workaround: Manually configure the SQL Server Database for encrypting communication.

Check your systems with an agent

Paste this into a coding or ops agent. It checks your systems read-only and reports a table per asset.

Check whether my systems are affected by CVE-2026-58114 (A vulnerability has been identified in SIMATIC BATCH V9.1 (All versions), SIMATIC Information Server 2020 (All versions), SIMATIC…), using the cve.now data below.

Rules: work read-only. Do not run exploit code, proof-of-concept scripts or scanners that send attack payloads, and do not change any configuration, package, image or deployment. Report findings only.

What cve.now has for CVE-2026-58114 (entry last updated 2026-11-10):
Affected:
- Siemens SIMATIC BATCH V9.1: all versions
- Siemens SIMATIC Information Server 2020: all versions
- Siemens SIMATIC Information Server 2022: all versions
- Siemens SIMATIC PCS 7 V9.1: all versions
- Siemens SIMATIC Process Historian 2020: all versions
- Siemens SIMATIC Process Historian 2022: all versions
- Siemens SIMATIC WinCC Runtime Professional V17: all versions
- Siemens SIMATIC WinCC Runtime Professional V18: all versions
- Siemens SIMATIC WinCC Runtime Professional V19: all versions
- Siemens SIMATIC WinCC Runtime Professional V20: all versions
- and 4 more affected products, listed on https://cve.now/CVE-2026-58114
Fixed versions: none listed yet.
Conditions (all must be true for the bug to be hit):
- Affected products include SIMATIC BATCH V9.1, Information Server 2020/2022, PCS 7 V9.1, Process Historian 2020/2022, WinCC V7.5/V8.0/V8.1 and WinCC Runtime Professional V17-V21 (all versions). (source: https://cert-portal.siemens.com/productcert/html/ssa-970803.html)
- Remote user authentication uses the deprecated NTLM protocol and is not properly secured. (source: https://cert-portal.siemens.com/productcert/html/ssa-970803.html)
- Kerberos is not used (for example, no domain with a Server Principal Name set). (source: https://cert-portal.siemens.com/productcert/html/ssa-970803.html)
Setup: unknown whether the bug needs a non-default feature or setting. Check the advisory.
Attacker needs: network access, no login, a user action.
Workaround: Manually configure the SQL Server Database for encrypting communication. (source: https://cert-portal.siemens.com/productcert/html/ssa-970803.html)
CISA KEV: CVE-2026-58114 is not listed as of cve.now's last read.
This KEV status is for CVE-2026-58114 only. If you also check another CVE, look up its own KEV status; never assume it from this one.

How to check:
- Installed software: check what is actually running, not what a repo declares. Read the version from each host, container image and Kubernetes node (the binary's version output, the OS package database, image layers), and check whether the conditions above hold there. Distribution packages may carry a backported fix under an older version number; confirm against the distribution's own advisory.

Verify against the linked advisories before concluding, and cite the date you read each one:
- https://cert-portal.siemens.com/productcert/html/ssa-970803.html
Do not conclude an asset is unaffected unless you checked it and the evidence covers both its version and the conditions above. If you could not check something, mark it unknown and say what is missing.

Report a table with one row per asset and these columns: Asset | Version or build | Status (affected, fixed, not applicable, unknown) | Compensating controls | Exposure (internet-facing, internal, none) | Evidence | Next action.

Entry: https://cve.now/CVE-2026-58114
For follow-up questions, use the cve.now MCP server at https://mcp.cve.now/mcp (no authentication), for example get_vulnerability with id CVE-2026-58114.

Timeline

  1. CVE published
  2. First seen by cve.now
  3. CISA SSVC assessment

    Exploitation: none · Automatable: no · Technical impact: total

  4. Record last updated

Affected versions

  • Siemens SIMATIC BATCH V9.1

    All versions

  • Siemens SIMATIC Information Server 2020

    All versions

  • Siemens SIMATIC Information Server 2022

    All versions

  • Siemens SIMATIC PCS 7 V9.1

    All versions

  • Siemens SIMATIC Process Historian 2020

    All versions

  • Siemens SIMATIC Process Historian 2022

    All versions

  • Siemens SIMATIC WinCC Runtime Professional V17

    All versions

  • Siemens SIMATIC WinCC Runtime Professional V18

    All versions

Show all 14 packagesShow fewer packages
  • Siemens SIMATIC WinCC Runtime Professional V19

    All versions

  • Siemens SIMATIC WinCC Runtime Professional V20

    All versions

  • Siemens SIMATIC WinCC Runtime Professional V21

    All versions

  • Siemens SIMATIC WinCC V7.5

    All versions

  • Siemens SIMATIC WinCC V8.0

    All versions

  • Siemens SIMATIC WinCC V8.1

    All versions

Evidence 3

Vendor advisory · 1

Establishes: Affected and fixed versions.

  1. Link

CVE record · 2

Establishes: The identifier and description.

  1. Record
  2. Record

Corrections

None so far.

Something wrong on this page? Report an error. Every fix is listed here.

Questions about CVE-2026-58114

Is CVE-2026-58114 being exploited?

It is not in CISA's Known Exploited Vulnerabilities catalog, and CISA's SSVC assessment does not mark exploitation as active. That does not mean it has not been attacked: vendors and researchers can report attacks before CISA lists them. No public exploit code is tracked.Source: cve.now feed data

What does this mean?

The affected products use the deprecated NTLM protocol for remote user authentication without properly securing it. An attacker positioned on the network path between systems can relay NTLM authentication and impersonate a legitimate user, taking over that user's session. The reach of such an attack depends on which services are accessible, such as a SQL server used by WinCC.Source: cert-portal.siemens.com

Which versions are affected by CVE-2026-58114?

SIMATIC BATCH V9.1: all versions. SIMATIC Information Server 2020: all versions. SIMATIC Information Server 2022: all versions. SIMATIC PCS 7 V9.1: all versions. SIMATIC Process Historian 2020: all versions. 9 more packages are listed on the page.Source: cve.now feed data

Am I affected, and how do I check?

The advisory lists all versions of SIMATIC BATCH V9.1, Information Server 2020 and 2022, PCS 7 V9.1, Process Historian 2020 and 2022, WinCC V7.5, V8.0 and V8.1, and WinCC Runtime Professional V17 through V21. The exposure applies when Kerberos is not used, for example when there is no domain with a Server Principal Name set. Check the product versions installed and whether the system joins a domain with an SPN configured.Source: cert-portal.siemens.com

How do I fix CVE-2026-58114?

No fixed version is available, so no upgrade target is named in the advisory. Follow the workaround of manually configuring the SQL Server database to encrypt communication, and assess the remaining risk where Kerberos is not used.Source: cert-portal.siemens.com

What if there's no patch?

Siemens states that currently no fix is planned. The available workaround is to manually configure the SQL Server database to encrypt its communication. Where Kerberos is not in use, the advisory asks the user to assess the corresponding risks.Source: cert-portal.siemens.com