A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.233.16-7862), Desigo PXC3 (All versions < V01.21.233.16-7862), Des
- Published
- Last modified
- Where the record stands: published, rejected by its publisher, or superseded by another id.What do these mean? →
- published
- Whether CISA lists it in its Known Exploited Vulnerabilities catalog: proof that attackers are using it.What do these mean? →
- Not listed in CISA KEV
- Fix
- Fixed in V01.21.233.16-7862, V02.21.194.36-2715
- Whether working attack code is public (Exploit-DB, Metasploit, Nuclei or GitHub). Public code makes attacks easier.What do these mean? →
- None on Exploit-DB, Metasploit or GitHub
- Exploitation: none
- Automatable: no
- Technical impact: partial
Summary
A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.233.16-7862), Desigo PXC3 (All versions < V01.21.233.16-7862), Desigo PXC4 (All versions < V02.21.194.36-2715), Desigo PXC5.E003 (All versions < V02.21.194.36-2715), Desigo PXC5.E24 (All versions < V02.21.194.36-2715), Desigo PXC7 (All versions < V02.21.194.36-2715). The affected devices are vulnerable to a denial-of-service (DoS) vulnerability. An attacker can exploit this issue by sending a malformed BACnet packet, causing the device to stop responding to BACnet queries. Recovery requires a device reset or reboot to restore normal functionality.
Timeline
- CVE published
- CISA SSVC assessment
Exploitation: none · Automatable: no · Technical impact: partial
- Record last updated
Affected versions
- Siemens Desigo DXR2
fixed in V01.21.233.16-7862
- Siemens Desigo PXC3
fixed in V01.21.233.16-7862
- Siemens Desigo PXC4
fixed in V02.21.194.36-2715
- Siemens Desigo PXC5.E003
fixed in V02.21.194.36-2715
- Siemens Desigo PXC5.E24
fixed in V02.21.194.36-2715
- Siemens Desigo PXC7
fixed in V02.21.194.36-2715