CVE-2026-58115
A vulnerability has been identified in SIMATIC IoT2050 Advanced (6ES7647-0BA00-1YA2) (All versions < V4.3.4.1 running Industrial OS with Nod
- Published
- Last modified
- Where the record stands: published, rejected by its publisher, or superseded by another id.What do these mean? →
- published
- Whether CISA lists it in its Known Exploited Vulnerabilities catalog: proof that attackers are using it.What do these mean? →
- Not listed in CISA KEV
- Fix
- Fixed in V4.3.4.1
- Whether working attack code is public (Exploit-DB, Metasploit, Nuclei or GitHub). Public code makes attacks easier.What do these mean? →
- None on Exploit-DB, Metasploit or GitHub
CISA's decision points: whether it is exploited, whether attacks can be automated, and how much control an attacker gets. Assessed (SSVC 2.0.3).What do these mean? →
- Exploitation: none
- Automatable: yes
- Technical impact: total
Summary
A vulnerability has been identified in SIMATIC IoT2050 Advanced (6ES7647-0BA00-1YA2) (All versions < V4.3.4.1 running Industrial OS with Node-RED installed). Affected devices do not enforce authentication on the Node-RED HTTP interface, allowing unauthenticated access to programming nodes that are capable of executing system commands on the server. This could allow an unauthenticated remote attacker to create malicious flows through the HTTP interface in order to execute arbitrary code on the underlying server with maximum privileges.
Timeline
- CVE published
- CISA SSVC assessment
Exploitation: none · Automatable: yes · Technical impact: total
- Record last updated
Affected versions
- Siemens SIMATIC IoT2050 Advanced
fixed in V4.3.4.1