BACnet Stack: Off-by-One Out-of-Bounds Read in ReadPropertyMultiple Object ID Decoder
- Published
- Last modified
- Where the record stands: published, rejected by its publisher, or superseded by another id.What do these mean? →
- published
- Whether CISA lists it in its Known Exploited Vulnerabilities catalog: proof that attackers are using it.What do these mean? →
- Not listed in CISA KEV
- Fix
- Fixed in 1.4.3
- Whether working attack code is public (Exploit-DB, Metasploit, Nuclei or GitHub). Public code makes attacks easier.What do these mean? →
- None on Exploit-DB, Metasploit or GitHub
- Exploitation: poc
- Automatable: yes
- Technical impact: partial
Summary
BACnet Stack is a BACnet open source protocol stack C library for embedded systems. Prior to 1.4.3, an off-by-one out-of-bounds read vulnerability in bacnet-stack's ReadPropertyMultiple service decoder allows unauthenticated remote attackers to read one byte past an allocated buffer boundary by sending a crafted RPM request with a truncated object identifier. The vulnerability is in rpm_decode_object_id(), which checks apdu_len < 5 but then accesses all 6 byte positions (indices 0-5) — consuming 1 byte for the context tag, 4 bytes for the object ID, then reading apdu[5] for the opening tag check. A 5-byte input passes the length check but causes a 1-byte OOB read, leading to crashes on embedded BACnet devices. The vulnerability exists in src/bacnet/rpm.c and affects any deployment that enables the ReadPropertyMultiple confirmed service handler (enabled by default in the reference server). This vulnerability is fixed in 1.4.3.
Timeline
- CVE published
- CISA SSVC assessment
Exploitation: poc · Automatable: yes · Technical impact: partial
- Record last updated
Affected versions
- bacnet-stack bacnet-stack
From 1.4.0 · fixed in 1.4.3