CVE-2025-7693
Rockwell Automation Micro800 Vulnerability
- Published
- Last modified
- Where the record stands: published, rejected by its publisher, or superseded by another id.What do these mean? →
- published
- Whether CISA lists it in its Known Exploited Vulnerabilities catalog: proof that attackers are using it.What do these mean? →
- Not listed in CISA KEV
- Whether working attack code is public (Exploit-DB, Metasploit, Nuclei or GitHub). Public code makes attacks easier.What do these mean? →
- None on Exploit-DB, Metasploit or GitHub
CISA's decision points: whether it is exploited, whether attacks can be automated, and how much control an attacker gets. Assessed (SSVC 2.0.3).What do these mean? →
- Exploitation: none
- Automatable: yes
- Technical impact: total
Summary
A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault.
Timeline
- CVE published
- CISA SSVC assessment
Exploitation: none · Automatable: yes · Technical impact: total
- Record last updated
Affected versions
- Rockwell Automation PLC - Micro850 L50E
V20.011 - V22.011