Skip to main content
← All vulnerabilities
CVE-2025-40944

A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF (6E

Published
Last modified
published
Not listed in CISA KEV
Fix
Fixed in V1.3, V6.0.1, V4.2.5, V4.2.2, V6.0.0
None on Exploit-DB, Metasploit or GitHub
  • Exploitation: none
  • Automatable: yes
  • Technical impact: partial

Summary

A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0) (All versions >= V4.2.0), SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0) (All versions), SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) (All versions < V1.3), SIMATIC ET 200SP IM 155-6 PN R1 (6ES7155-6AU00-0HM0) (All versions < V6.0.1), SIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0) (All versions >= V4.2.0 < V4.2.5), SIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0) (All versions < V4.2.2), SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0) (All versions), SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0) (All versions < V6.0.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0) (All versions < V6.0.0). Affected devices do not properly handle S7 protocol session disconnect requests. When receiving a valid S7 protocol Disconnect Request (COTP DR TPDU) on TCP port 102, the devices enter an improper session state. This could allow an attacker to cause the device to become unresponsive, leading to a denial-of-service condition that requires a power cycle to restore normal operation.

Timeline

  1. CVE published
  2. CISA SSVC assessment

    Exploitation: none · Automatable: yes · Technical impact: partial

  3. Record last updated

Affected versions

  • Siemens SIMATIC ET 200AL IM 157-1 PN

    All versions

  • Siemens SIMATIC ET 200MP IM 155-5 PN HF

    From V4.2.0

  • Siemens SIMATIC ET 200SP IM 155-6 MF HF

    All versions

  • Siemens SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants)

    fixed in V1.3

  • Siemens SIMATIC ET 200SP IM 155-6 PN R1

    fixed in V6.0.1

  • Siemens SIMATIC ET 200SP IM 155-6 PN/2 HF

    From V4.2.0 · fixed in V4.2.5

  • Siemens SIMATIC ET 200SP IM 155-6 PN/3 HF

    fixed in V4.2.2

  • Siemens SIMATIC PN/MF Coupler

    All versions

  • Siemens SIMATIC PN/PN Coupler

    fixed in V6.0.0

  • Siemens SIPLUS ET 200MP IM 155-5 PN HF

    From V4.2.0

  • Siemens SIPLUS ET 200MP IM 155-5 PN HF

    From V4.2.0

  • Siemens SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL

    From V4.2.0

  • Siemens SIPLUS ET 200SP IM 155-6 PN HF

    From V4.2.0 · fixed in V4.2.5

  • Siemens SIPLUS ET 200SP IM 155-6 PN HF

    From V4.2.0 · fixed in V4.2.5

  • Siemens SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL

    From V4.2.0 · fixed in V4.2.5

  • Siemens SIPLUS ET 200SP IM 155-6 PN HF TX RAIL

    From V4.2.0 · fixed in V4.2.5

  • Siemens SIPLUS NET PN/PN Coupler

    fixed in V6.0.0

References 1

cert-portal.siemens.com