CVE-2025-40556
A vulnerability has been identified in BACnet ATEC 550-440 (All versions), BACnet ATEC 550-441 (All versions), BACnet ATEC 550-445 (All vers
- Published
- Last modified
- Where the record stands: published, rejected by its publisher, or superseded by another id.What do these mean? →
- published
- Whether CISA lists it in its Known Exploited Vulnerabilities catalog: proof that attackers are using it.What do these mean? →
- Not listed in CISA KEV
- Whether working attack code is public (Exploit-DB, Metasploit, Nuclei or GitHub). Public code makes attacks easier.What do these mean? →
- None on Exploit-DB, Metasploit or GitHub
CISA's decision points: whether it is exploited, whether attacks can be automated, and how much control an attacker gets. Assessed (SSVC 2.0.3).What do these mean? →
- Exploitation: none
- Automatable: no
- Technical impact: partial
Summary
A vulnerability has been identified in BACnet ATEC 550-440 (All versions), BACnet ATEC 550-441 (All versions), BACnet ATEC 550-445 (All versions), BACnet ATEC 550-446 (All versions). Affected devices improperly handle specific incoming BACnet MSTP messages. This could allow an attacker residing in the same BACnet network to send a specially crafted MSTP message that results in a denial of service condition of the targeted device. A power cycle is required to restore the device's normal operation.
Timeline
- CVE published
- CISA SSVC assessment
Exploitation: none · Automatable: no · Technical impact: partial
- Record last updated
Affected versions
- Siemens BACnet ATEC 550-440
All versions
- Siemens BACnet ATEC 550-441
All versions
- Siemens BACnet ATEC 550-445
All versions
- Siemens BACnet ATEC 550-446
All versions