Inductive Automation Ignition Execution with Unnecessary Privileges
- Published
- Last modified
- Where the record stands: published, rejected by its publisher, or superseded by another id.What do these mean? →
- published
- Whether CISA lists it in its Known Exploited Vulnerabilities catalog: proof that attackers are using it.What do these mean? →
- Not listed in CISA KEV
- Whether working attack code is public (Exploit-DB, Metasploit, Nuclei or GitHub). Public code makes attacks easier.What do these mean? →
- None on Exploit-DB, Metasploit or GitHub
- Exploitation: none
- Automatable: no
- Technical impact: total
Summary
Ignition by Inductive Automation, when installed with default OS service account settings, may expose the host system to an elevated code execution risk via the gateway backup restore functionality. An authenticated user with Gateway Administrator privileges can import a malicious gateway backup (.gwbk) file containing crafted project resources, scripts, or modules, resulting in code execution on the host system. This affects both Windows and Linux installations. On Windows, default installations often run the Ignition service as NT AUTHORITY\SYSTEM, resulting in code execution with full local system privileges. On Linux, default installations commonly run the Ignition service as root or with elevated privileges. Specific privilege level depends on installation configuration.
Timeline
- CVE published
- CISA SSVC assessment
Exploitation: none · Automatable: no · Technical impact: total
- Record last updated
Affected versions
- Inductive Automation Ignition
8.1.x, 8.3.x