Information Disclosure, Information Tampering and Denial of Service (DoS) Vulnerability in GENESIS64, ICONICS Suite, MC Works64, and GENESIS32
- Published
- Last modified
- Where the record stands: published, rejected by its publisher, or superseded by another id.What do these mean? →
- published
- Whether CISA lists it in its Known Exploited Vulnerabilities catalog: proof that attackers are using it.What do these mean? →
- Not listed in CISA KEV
- Whether working attack code is public (Exploit-DB, Metasploit, Nuclei or GitHub). Public code makes attacks easier.What do these mean? →
- None on Exploit-DB, Metasploit or GitHub
- Exploitation: none
- Automatable: no
- Technical impact: total
Summary
Incorrect Default Permissions vulnerability in GenBroker32, which is included in the installers for Mitsubishi Electric GENESIS64 versions 10.97.3 and prior, Mitsubishi Electric Iconics Digital Solutions GENESIS64 versions 10.97.3 and prior, Mitsubishi Electric ICONICS Suite versions 10.97.3 and prior, Mitsubishi Electric Iconics Digital Solutions ICONICS Suite versions 10.97.3 and prior, Mitsubishi Electric GENESIS32 versions 9.70.300.23 and prior, Mitsubishi Electric Iconics Digital Solutions GENESIS32 versions 9.70.300.23 and prior, and Mitsubishi Electric MC Works64 all versions allows a local authenticated attacker to disclose or tamper with confidential information and data contained in the products, or cause a denial of service (DoS) condition on the products, by accessing a folder with incorrect permissions, when GenBroker32 is installed on the same PC as GENESIS64, ICONICS Suite, MC Works64, or GENESIS32.
Timeline
- CVE published
- CISA SSVC assessment
Exploitation: none · Automatable: no · Technical impact: total
- Record last updated
Affected versions
- Mitsubishi Electric Corporation GENESIS64
Version range not reported
- Mitsubishi Electric Corporation MC Works64
All versions
- Mitsubishi Electric Iconics Digital Solutions GENESIS64
Version range not reported
- Mitsubishi Electric Corporation ICONICS Suite
Version range not reported
- Mitsubishi Electric Iconics Digital Solutions ICONICS Suite
Version range not reported
- Mitsubishi Electric Corporation GENESIS32
Version range not reported
- Mitsubishi Electric Iconics Digital Solutions GENESIS32
Version range not reported