Skip to main content
← All vulnerabilities
CVE-2022-4608

A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product.

Published
Last modified
published
Not listed in CISA KEV
None on Exploit-DB, Metasploit or GitHub
  • Exploitation: none
  • Automatable: yes
  • Technical impact: partial

Summary

A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow.

Timeline

  1. CVE published
  2. CISA SSVC assessment

    Exploitation: none · Automatable: yes · Technical impact: partial

  3. Record last updated

Affected versions

  • Hitachi Energy RTU500 series

    RTU500 series CMU Firmware version 13.3.1, RTU500 series CMU Firmware version 13.3.2

References 1

publisher.hitachienergy.com