A vulnerability has been identified in Desigo PXM30-1 (All versions < V02.20.126.11-41), Desigo PXM30.E (All versions < V02.20.126.11-41), D
- Published
- Last modified
- Where the record stands: published, rejected by its publisher, or superseded by another id.What do these mean? →
- published
- Whether CISA lists it in its Known Exploited Vulnerabilities catalog: proof that attackers are using it.What do these mean? →
- Not listed in CISA KEV
- Whether working attack code is public (Exploit-DB, Metasploit, Nuclei or GitHub). Public code makes attacks easier.What do these mean? →
- None on Exploit-DB, Metasploit or GitHub
Summary
A vulnerability has been identified in Desigo PXM30-1 (All versions < V02.20.126.11-41), Desigo PXM30.E (All versions < V02.20.126.11-41), Desigo PXM40-1 (All versions < V02.20.126.11-41), Desigo PXM40.E (All versions < V02.20.126.11-41), Desigo PXM50-1 (All versions < V02.20.126.11-41), Desigo PXM50.E (All versions < V02.20.126.11-41), PXG3.W100-1 (All versions < V02.20.126.11-37), PXG3.W100-2 (All versions < V02.20.126.11-41), PXG3.W200-1 (All versions < V02.20.126.11-37), PXG3.W200-2 (All versions < V02.20.126.11-41). There exists an Improper Neutralization of Special Elements used in an OS Command with root privileges during a restore operation due to the missing validation of the names of files included in the input package. By restoring a specifically crafted package, a remote low-privileged attacker can execute arbitrary system commands with root privileges on the device, leading to a full compromise.
Timeline
- CVE published
- Record last updated
Affected versions
- Siemens Desigo PXM30-1
All versions < V02.20.126.11-41
- Siemens Desigo PXM30.E
All versions < V02.20.126.11-41
- Siemens Desigo PXM40-1
All versions < V02.20.126.11-41
- Siemens Desigo PXM40.E
All versions < V02.20.126.11-41
- Siemens Desigo PXM50-1
All versions < V02.20.126.11-41
- Siemens Desigo PXM50.E
All versions < V02.20.126.11-41
- Siemens PXG3.W100-1
All versions < V02.20.126.11-37
- Siemens PXG3.W100-2
All versions < V02.20.126.11-41
- Siemens PXG3.W200-1
All versions < V02.20.126.11-37
- Siemens PXG3.W200-2
All versions < V02.20.126.11-41