Skip to main content
← All vulnerabilities
CVE-2022-31204

Omron CS series, CJ series, and CP series PLCs through 2022-05-18 use cleartext passwords.

Published
Last modified
published
Not listed in CISA KEV
None on Exploit-DB, Metasploit or GitHub

Summary

Omron CS series, CJ series, and CP series PLCs through 2022-05-18 use cleartext passwords. They feature a UM Protection setting that allows users or system integrators to configure a password in order to restrict sensitive engineering operations (such as project/logic uploads and downloads). This password is set using the OMRON FINS command Program Area Protect and unset using the command Program Area Protect Clear, both of which are transmitted in cleartext.

Timeline

  1. CVE published
  2. Record last updated

Affected versions

  • n/a n/a

    Version range not reported

References 2

forescout.com

cisa.gov