Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass.

Published
Last modified
published
Not listed in CISA KEV
None on Exploit-DB, Metasploit or GitHub
  • Exploitation: none
  • Automatable: no
  • Technical impact: total

Summary

Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. According to FSCT-2022-0062, there is a Saia Burgess Controls (SBC) PCD S-Bus authentication bypass issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication functions on the basis of a MAC/IP whitelist with inactivity timeout to which an authenticated client's MAC/IP is stored. UDP traffic can be spoofed to bypass the whitelist-based access control. Since UDP is stateless, an attacker capable of passively observing traffic can spoof arbitrary messages using the MAC/IP of an authenticated client. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration.

Timeline

  1. CVE published
  2. CISA SSVC assessment

    Exploitation: none · Automatable: no · Technical impact: total

  3. Record last updated

Affected versions

  • n/a n/a

    Version range not reported

References 2

forescout.com

cisa.gov