JTEKT TOYOPUC PLCs through 2022-04-29 do not ensure data integrity.
- Published
- Last modified
- Where the record stands: published, rejected by its publisher, or superseded by another id.What do these mean? →
- published
- Whether CISA lists it in its Known Exploited Vulnerabilities catalog: proof that attackers are using it.What do these mean? →
- Not listed in CISA KEV
- Whether working attack code is public (Exploit-DB, Metasploit, Nuclei or GitHub). Public code makes attacks easier.What do these mean? →
- None on Exploit-DB, Metasploit or GitHub
Summary
JTEKT TOYOPUC PLCs through 2022-04-29 do not ensure data integrity. They utilize the unauthenticated CMPLink/TCP protocol for engineering purposes, including downloading projects and control logic to the PLC. Control logic is downloaded to the PLC on a block-by-block basis with a given memory address and a blob of machine code. The logic that is downloaded to the PLC is not cryptographically authenticated, allowing an attacker to execute arbitrary machine code on the PLC's CPU module in the context of the runtime. In the case of the PC10G-CPU, and likely for other CPU modules of the TOYOPUC family, a processor without MPU or MMU is used and this no memory protection or privilege-separation capabilities are available, giving an attacker full control over the CPU.
Timeline
- CVE published
- Record last updated
Affected versions
- n/a n/a
Version range not reported