Skip to main content
← All vulnerabilities
CVE-2021-35534

Insufficient Security Control Vulnerability

Published
Last modified
published
Not listed in CISA KEV
Fix
Fixed in 2.2.3.5, 2.2.5.2, 1.3.0.8
None on Exploit-DB, Metasploit or GitHub

Summary

Insufficient security control vulnerability in internal database access mechanism of Hitachi Energy Relion 670/650/SAM600-IO, Relion 650, GMS600, PWC600 allows attacker who successfully exploited this vulnerability, of which the product does not sufficiently restrict access to an internal database tables, could allow anybody with user credentials to bypass security controls that is enforced by the product. Consequently, exploitation may lead to unauthorized modifications on data/firmware, and/or to permanently disabling the product. This issue affects: Hitachi Energy Relion 670 Series 2.0 all revisions; 2.2.2 all revisions; 2.2.3 versions prior to 2.2.3.5. Hitachi Energy Relion 670/650 Series 2.1 all revisions. 2.2.0 all revisions; 2.2.4 all revisions; Hitachi Energy Relion 670/650/SAM600-IO 2.2.1 all revisions; 2.2.5 versions prior to 2.2.5.2. Hitachi Energy Relion 650 1.0 all revisions. 1.1 all revisions; 1.2 all revisions; 1.3 versions prior to 1.3.0.8; Hitachi Energy GMS600 1.3.0; 1.3.0.1; 1.2.0. Hitachi Energy PWC600 1.0.1 version 1.0.1.4 and prior versions; 1.1.0 version 1.1.0.1 and prior versions.

Timeline

  1. CVE published
  2. Record last updated

Affected versions

  • Hitachi Energy Relion 670 Series

    From 2.2.3 · fixed in 2.2.3.5

  • Hitachi Energy Relion 670/650 Series

    2.2.0 all revisions, 2.2.4 all revisions, 2.1 all revisions

  • Hitachi Energy Relion 670/650/SAM600-IO

    From 2.2.5 · fixed in 2.2.5.2

  • Hitachi Energy Relion 650

    From 1.3 · fixed in 1.3.0.8

  • Hitachi Energy GMS600

    1.3.0, 1.3.1.0 1.3.0.1, 1.2.0

  • Hitachi Energy PWC600

    From 1.0.1 · through 1.0.1.4; From 1.1.0 · through 1.1.0.1

References 3

search.abb.com