Skip to main content
← All vulnerabilities
CVE-2021-35533

Specially Crafted IEC 60870-5-104 Packet Vulnerability in RTU500 series

Published
Last modified
published
Not listed in CISA KEV
None on Exploit-DB, Metasploit or GitHub

Summary

Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions).

Timeline

  1. CVE published
  2. Record last updated

Affected versions

  • Hitachi Energy RTU500 series

    From CMU Firmware version 12.0; From CMU Firmware version 12.2; From CMU Firmware version 12.4

References 1

search.abb.com