Skip to main content
← All vulnerabilities
CVE-2019-19279

A vulnerability has been identified in SIPROTEC 4 and SIPROTEC Compact relays equipped with EN100 Ethernet communication modules (All versio

Published
Last modified
published
Not listed in CISA KEV
None on Exploit-DB, Metasploit or GitHub

Summary

A vulnerability has been identified in SIPROTEC 4 and SIPROTEC Compact relays equipped with EN100 Ethernet communication modules (All versions). Specially crafted packets sent to port 50000/UDP of the EN100 Ethernet communication modules could cause a Denial-of-Service of the affected device. A manual reboot is required to recover the service of the device. At the time of advisory publication no public exploitation of this security vulnerability was known to Siemens.

Timeline

  1. CVE published
  2. Record last updated

Affected versions

  • Siemens AG SIPROTEC 4 and SIPROTEC Compact relays equipped with EN100 Ethernet communication modules

    All versions

References 1

cert-portal.siemens.com