Skip to main content
← All vulnerabilities
CVE-2018-4842

A vulnerability has been identified in SCALANCE X-200IRT switch family (incl.

Published
Last modified
published
Not listed in CISA KEV
None on Exploit-DB, Metasploit or GitHub

Summary

A vulnerability has been identified in SCALANCE X-200IRT switch family (incl. SIPLUS NET variants) (All versions < V5.4.1), SCALANCE X-200RNA switch family (All versions < V3.2.7), SCALANCE X-300 switch family (incl. X408 and SIPLUS NET variants) (All versions < V4.1.3). A remote, authenticated attacker with access to the configuration web server could be able to store script code on the web site, if the HRP redundancy option is set. This code could be executed in the web browser of victims visiting this web site (XSS), affecting its confidentiality, integrity and availability. User interaction is required for successful exploitation, as the user needs to visit the manipulated web site. At the stage of publishing this security advisory no public exploitation is known. The vendor has confirmed the vulnerability and provides mitigations to resolve it.

Timeline

  1. CVE published
  2. Record last updated

Affected versions

  • Siemens SCALANCE X-200IRT switch family (incl. SIPLUS NET variants)

    All versions < V5.4.1

  • Siemens SCALANCE X-200RNA switch family

    All versions < V3.2.7

  • Siemens SCALANCE X-300 switch family (incl. X408 and SIPLUS NET variants)

    All versions < V4.1.3

References 2

securityfocus.com

cert-portal.siemens.com