A vulnerability has been identified in SIMATIC S7-300 CPUs (All versions < V3.X.16).
- Published
- Last modified
- Where the record stands: published, rejected by its publisher, or superseded by another id.What do these mean? →
- published
- Whether CISA lists it in its Known Exploited Vulnerabilities catalog: proof that attackers are using it.What do these mean? →
- Not listed in CISA KEV
- Whether working attack code is public (Exploit-DB, Metasploit, Nuclei or GitHub). Public code makes attacks easier.What do these mean? →
- None on Exploit-DB, Metasploit or GitHub
- Exploitation: none
- Automatable: yes
- Technical impact: partial
Summary
A vulnerability has been identified in SIMATIC S7-300 CPUs (All versions < V3.X.16). The affected CPUs improperly validate S7 communication packets which could cause a Denial-of-Service condition of the CPU. The CPU will remain in DEFECT mode until manual restart. Successful exploitation requires an attacker to be able to send a specially crafted S7 communication packet to a communication interface of the CPU. This includes Ethernet, PROFIBUS, and Multi Point Interfaces (MPI). No user interaction or privileges are required to exploit the security vulnerability. The vulnerability could allow causing a Denial-of-Service condition of the core functionality of the CPU, compromising the availability of the system. At the time of advisory publication no public exploitation of this security vulnerability was known. Siemens confirms the security vulnerability and provides mitigations to resolve the security issue.
Timeline
- CVE published
- CISA SSVC assessment
Exploitation: none · Automatable: yes · Technical impact: partial
- Record last updated
Affected versions
- Siemens SIMATIC S7-300 CPUs
All versions < V3.X.16