A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMA
- Published
- Last modified
- Where the record stands: published, rejected by its publisher, or superseded by another id.What do these mean? →
- published
- Whether CISA lists it in its Known Exploited Vulnerabilities catalog: proof that attackers are using it.What do these mean? →
- Not listed in CISA KEV
- Whether working attack code is public (Exploit-DB, Metasploit, Nuclei or GitHub). Public code makes attacks easier.What do these mean? →
- None on Exploit-DB, Metasploit or GitHub
Summary
A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-2 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-2 DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 417-4 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions < V7.0.3), SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.2.1), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 V7 (All versions), SIPLUS S7-400 CPU 417-4 V7 (All versions). Specially crafted packets sent to port 102/tcp via Ethernet interface, via PROFIBUS, or via Multi Point Interfaces (MPI) could cause the affected devices to go into defect mode. Manual reboot is required to resume normal operation. Successful exploitation requires an attacker to be able to send specially crafted packets to port 102/tcp via Ethernet interface, via PROFIBUS or Multi Point Interfaces (MPI). No user interaction and no user privileges are required to exploit the security vulnerability. The vulnerability could allow causing a denial of service condition of the core functionality of the CPU, compromising the availability of the system.
Timeline
- CVE published
- Record last updated
Affected versions
- Siemens SIMATIC S7-400 CPU 412-1 DP V7
All versions
- Siemens SIMATIC S7-400 CPU 412-2 DP V7
All versions
- Siemens SIMATIC S7-400 CPU 414-2 DP V7
All versions
- Siemens SIMATIC S7-400 CPU 414-3 DP V7
All versions
- Siemens SIMATIC S7-400 CPU 414-3 PN/DP V7
All versions < V7.0.3
- Siemens SIMATIC S7-400 CPU 414F-3 PN/DP V7
All versions < V7.0.3
- Siemens SIMATIC S7-400 CPU 416-2 DP V7
All versions
- Siemens SIMATIC S7-400 CPU 416-3 DP V7
All versions
- Siemens SIMATIC S7-400 CPU 416-3 PN/DP V7
All versions < V7.0.3
- Siemens SIMATIC S7-400 CPU 416F-2 DP V7
All versions
- Siemens SIMATIC S7-400 CPU 416F-3 PN/DP V7
All versions < V7.0.3
- Siemens SIMATIC S7-400 CPU 417-4 DP V7
All versions
- Siemens SIMATIC S7-400 CPU 412-2 PN V7
All versions < V7.0.3
- Siemens SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants)
All versions
- Siemens SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants)
All versions < V6.0.9
- Siemens SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants)
All versions
- Siemens SIMATIC S7-410 CPU family (incl. SIPLUS variants)
All versions < V8.2.1
- Siemens SIPLUS S7-400 CPU 414-3 PN/DP V7
All versions < V7.0.3
- Siemens SIPLUS S7-400 CPU 416-3 PN/DP V7
All versions < V7.0.3
- Siemens SIPLUS S7-400 CPU 416-3 V7
All versions
- Siemens SIPLUS S7-400 CPU 417-4 V7
All versions