Skip to main content
← All vulnerabilities
CVE-2015-5374

A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Mo

Published
Last modified
published
Not listed in CISA KEV
1 on Exploit-DB, 1 Metasploit module, 1 proof of concept on GitHub

Summary

A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. Specially crafted packets sent to port 50000/UDP could cause a denial-of-service of the affected device. A manual reboot may be required to recover the service of the device.

Timeline

  1. CVE published
  2. Public exploit on Exploit-DB

    EDB-44103

  3. Record last updated
  4. EPSS reached 10%

    FIRST estimates at least a 10% chance of exploitation in the next 30 days

Affected versions

  • n/a n/a

    Version range not reported

References 9

siemens.com

Exploit-DB

ics-cert.us-cert.gov

securityfocus.com

GitHub · rapid7/metasploit-framework

GitHub · can/CVE-2015-5374-DoS-PoC